PowerControl & PowerAssist Yes
Transfer switch 50 A
INVERTER
Input voltage range 19 – 33 V / 38 – 66 V
Output Output voltage: 230 VAC ± 2%
Frequency: 50 Hz ± 0,1% (1)
Cont. output power at 25°C (3) 3000 VA
Cont. output power at 25°C 2400 W
Cont. output power at 40°C 2200 W
Cont. output power at 65°C 1700 W
Peak power (W) 6000 W
Maximum efficiency 94 / 95 %
Zero load power 20 / 25 W
Zero load power in AES mode 15 / 20 W
Zero load power in Search mode 10 / 12 W
CHARGER
AC Input Input voltage range: 187-265 VAC
Input frequency: 45 – 65 Hz
Charge voltage ‘absorption’ 28,8 / 57,6 V
Charge voltage ‘float’ 27,6 / 55,2 V
Storage mode 26,4 / 52,8 V
Maximum battery charge current (4) 70 / 35 A
Battery temperature sensor yes
GENERAL
Auxiliary output Yes (16 A) Switches off when no external AC source available
Programmable relay (5) Yes
Protection (2) a – g
VE.Bus communication port For parallel and three phase operation,
remote monitoring and system integration
General purpose com. port Yes
Remote on-off Yes
Operating temperature range -40 to +65°C (fan assisted cooling)
Humidity (non-condensing) max 95%
ENCLOSURE
Material & Colour Aluminium, blue RAL 5012
Protection category IP 21
Battery-connection Four M8 bolts
(2 plus and 2 minus connections)
230 V AC-connection Screw terminals 13 mm² (6 AWG)
Weight 18 kg
Dimensions (hxwxd) 362 x 258 x 218 mm
STANDARDS
Safety EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2
Emission, Immunity EN 55014-1, EN 55014-2, EN-IEC 61000-3-2, EN-IEC 61000-3-3
IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3
Uninterruptible power supply IEC 62040-1, AS 620401.1
Anti-islanding VDE-AR-N 4105, AS/NZS 4777.2, NRS 097-2-1, UTE C15-712-1, C10/11, RD 1699-RD 413, TOR D4